| SNAP-AIARMS-i SNAP Isolated 2-Ch 0-10 amp RMS Analog Input Module |
|
input is the 5-amp secondary of a standard current transformer used to monitor AC line current. The module may also be
used to monitor AC current to greater than a 100-amp range, using a current transformer of suitable ratio.
The two channels are isolated from each other; they do not share any field connection. The SNAP-AIARMS-i module is an
excellent choice for differential current measurements.
If you need Factory Mutual approval, choose the SNAP-AIARMS-i-FM instead.
If you do not need channel-to-channel isolation, see SNAP-AIARMS.
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted
controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for PC-
based control or for use as intelligent remote I/O for an Allen-Bradley Logix PLC system, such as ControlLogix,
MicroLogix, or CompactLogix.
| Input Range | 0 to 10 amp RMS AC/DC |
| Input Over-Range | To 11 amps |
| Input Resistance | 0.005 ohms |
| Maximum Input | 11 amps AC/DC |
| Accuracy (AC) | ±8 mA and ±0.2% reading |
| Resolution | 400 µA |
| DC Reversal | ±16 mA (0.16%) |
| Input Response Time (Step Change) | 63.2% (6.32 A) in 50 mS 99% (9.92 A) in 75 mS |
| DC Common Mode Rejection | >-120 dB |
| AC Common Mode Rejection | >-120 dB at 60 Hz |
| Maximum Operating Voltage Between Channels Common Mode Voltage | 250 V 250 V |
| Isolation: Optical | 4000 V |
| Isolation: Transformer | 1500 V |
| Isolation: Channel to Channel | 250 V continuous (1500 V transient) |
| Power Requirements | 5 VDC (±0.15 V) at 200 mA |
| Ambient Temperature: Operating Storage | 0 °C to 70 °C -25 °C to 85 °C |
| Torque, hold-down screws | 4 in-lb (0.45 N-m) |
| Torque, connector screws | 5.26 in-lb (0.6 N-m) |
| Agency Approvals | CE, RoHS, DFARS FM (SNAP-AIARMS-FM only) |
| Warranty | Lifetime |