32102-6 Power Supply PS1100 (24V, 100W), DIN RAIL
This 24V, 100W DIN rail power supply is a slim-design, DIN rail mounted Class I switching power supply, with an extended temperature range
Part Number: 32102-6
- Universal AC input
- Short circuit, overload, over voltage protection
- Air convection cooling
- DIN rail installation
- Built in DC OK active signal
- NEC class 2/ LPS compliant
- Power on LED indicator
- No load power consumption < 1W
- 100% full burn-in tested
System Specifications
Hardware
- EnclosureUL Compliant fully isolated plastic
- Installation MethodDIN rail (35MM)
- DIN Rail SpecTS35/7.5 or TS35/15
- LED IndicatorsOutput voltage status
- Dimensions3.9" x 2.2" x 3.5"
9.91 x 5.59 x 8.89 cm - Product Weight0.9 lbs
408.23 g
Input Specifications
- Connector TypeScrew Terminals
- AC Voltage Range85-264VAC
- Frequency Range47-63Hz
- Power Factor (PF Typ.)≥0.95/230VAC
≥0.98/115VAC - DC Voltage120-370VDC
- Efficiency (Typ.)87%
- AC Current (Typ.)1.3A/115VAC
0.8A/230VAC - Cold Start Inrush Current30A/115VAC
60A/230VAC - Leakage Current< 1mA/240VAC
- No Load Power Consumption< 1W
Output Specifications
- Connector TypeScrew Terminals
- DC Voltage24VDC
- Rated Current4A
- Current Range0-4A
- Rated Power96W
- Voltage Adjustable Range24 - 30VDC
- Voltage Tolerance±1%
- Ripple and Noise (Max)150mVp-p
- Output Load Derating60% of full load at 60°C
- Line Regulation±1%
- Load Regulation±1%
- Set-Up, Rise Time3000ms, 50ms/230VAC
3000ms, 30ms/115VAC - Hold Up Time (Typ.)50ms/230VAC
20ms/115VAC at full load - DC OK Active SignalRelay Contact Rating: 30/1A
Protection Specifications
- Short Circuit/Overload
- Overload Power105-150% of rated power, 100W
- Overload Protection TypeConstant current limiting. Recovers automatically after fault condition is removed.
- Over Voltage
- Rated Voltage31.2-36VDC
- Over Voltage Protection TypeShutdown output voltage, re-power on to recover
- Over Temperature
- Rated Temperature90°C ± 10°C detection on power transistor heat sink
- Over Temperature Protection TypeShutdown output voltage, re-power on to recover
Environmental Specifications
- Air temperature
- System On-10 to 60° C
- System Off-40 to 85° C
- Vibration
- Component10-500Hz, 2G 10 min./1 cycle, 60 min. each along X, Y, Z axes
- MountingCompliance to IEC60068-2-6
- Operating Humidity (non-condensing)20% to 90%
- MTBF (Mean Time Between Failures)39.5 Years
Export Information
- Packaged Shipping Weightl.0 lbs
458.13 g - Package Dimensions4.5" x 2.5" x 4.1"
11.43 x 6.35 x 10.41 cm - UPC Code7-56727-32102-6
- ECCN4A994
- Schedule B Number8504.40.6007
Regulatory Approvals
- EmissionsEuropean Standard EN61204-3
European Standard EN55022
Class B Limit
IEC 1000-3-2/EN61000-3-2: Harmonic
Class A Limit
IEC 1000-3-2/EN61000-3-2: Flicker - ImmunityEuropean Standard EN61204-3
European Standard EN55024:
IEC 1000-4-2/EN61000-4-2: Electrostatic Discharge (ESD)
IEC 1000-4-3/EN61000-4-3: Radiated Radio-Frequency (RF)
IEC 1000-4-4/EN61000-4-4: Fast Transient/Burst
IEC 1000-4-5/EN61000-4-5: Surge
IEC 1000-4-6/EN61000-4-6: Conducted Disturbance
IEC 1000-4-8/EN61000-4-8: Magnetic field
IEC 1000-4-11/EN61000-4-11: Dips and Voltage Variations - SafetyUL 60950
- OtherEuropean Standard: 2002/95/EC Directive (RoHS)
- Regulatory Approvals