Units | G4ODC5 G4ODC5FM* | G4ODC5A G4ODC5AFM | G4ODC5MA | G4ODC15 | G4ODC24 | G4ODC24A | |
Maximum line voltage | VDC | 60 | 200 | 60 | 60 | 60 | 200 |
Output voltage range | VDC | 5-60 | 5-200 | 5-60 | 5-60 | 5-60 | 5-200 |
Key feature | | | | Diagnostic switch | | | |
Current rating: At 45 °C ambient At 70 °C ambient | A A | 3 2 | 1 0.55 | 3 2 | 3 2 | 3 2 | 1 0.55 |
Isolation input-to-output (transient): 1 ms 1 minute | volts | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 |
Off-state leakage at nominal voltage (60 Hz) | mA | 1 | 1 | 1 | 1 | 1 | 1 |
Control Resistance (RC in schematic) | W | 220 | 220 | 220 | 1 K | 2.2 K | 2.2 K |
One-second surge | A | 5 | 5 | 5 | 5 | 5 | 5 |
Turn-on time | micro- seconds | 100 | 100 | 100 | 100 | 100 | 100 |
Turn-off time | micro- seconds | 750 | 750 | 750 | 750 | 750 | 750 |
Nominal logic voltage | VDC | 5 | 5 | 5 | 15 | 24 | 24 |
Logic voltage range | VDC | 4-8 | 4-8 | 4-8 | 10.5-16 | 19.5-32 | 19.5-32 |
Logic pickup voltage | VDC | 4 | 4 | 4 | 10.5 | 19.5 | 19.5 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 | 1 |
Logic input current at nominal logic voltage | mA | 12 | 12 | 12 | 15 | 18 | 18 |
Temperature Operating: Storage: | °C °C | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 |