G4ODC5AFM G4 DC Output 5-200 VDC, 5 VDC Logic, Factory Mutual Approved |
(transient) between field devices and control logic.
Typical applications for DC output modules include switching loads such as DC relays, solenoids, motor starters, lamps,
and indicators.
The G4ODC5AFM is Factory Mutual approved. If you do not need FM approval, see the G4ODC5A.
Units | G4ODC5 G4ODC5FM* | G4ODC5A G4ODC5AFM | G4ODC5MA | G4ODC15 | G4ODC24 | G4ODC24A | |
Maximum line voltage | VDC | 60 | 200 | 60 | 60 | 60 | 200 |
Output voltage range | VDC | 5-60 | 5-200 | 5-60 | 5-60 | 5-60 | 5-200 |
Key feature | | | | Diagnostic switch | | | |
Current rating: At 45 °C ambient At 70 °C ambient | A A | 3 2 | 1 0.55 | 3 2 | 3 2 | 3 2 | 1 0.55 |
Isolation input-to-output (transient): 1 ms 1 minute | volts | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 | 4000 1500 |
Off-state leakage at nominal voltage (60 Hz) | mA | 1 | 1 | 1 | 1 | 1 | 1 |
Control Resistance (RC in schematic) | W | 220 | 220 | 220 | 1 K | 2.2 K | 2.2 K |
One-second surge | A | 5 | 5 | 5 | 5 | 5 | 5 |
Turn-on time | micro- seconds | 100 | 100 | 100 | 100 | 100 | 100 |
Turn-off time | micro- seconds | 750 | 750 | 750 | 750 | 750 | 750 |
Nominal logic voltage | VDC | 5 | 5 | 5 | 15 | 24 | 24 |
Logic voltage range | VDC | 4-8 | 4-8 | 4-8 | 10.5-16 | 19.5-32 | 19.5-32 |
Logic pickup voltage | VDC | 4 | 4 | 4 | 10.5 | 19.5 | 19.5 |
Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 | 1 |
Logic input current at nominal logic voltage | mA | 12 | 12 | 12 | 15 | 18 | 18 |
Temperature Operating: Storage: | °C °C | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 | -30 to +70 -30 to +85 |
* Part numbers ending in FM are Factory Mutual approved. |
We will inform you if the price of this product will be changed according to your wished price.
Review product
No review available for this product.