AD12 -10 To +10 VDC Input |
| AD11 | AD12 | AD13T |
Nominal Voltage Input | -5 to + 5 VDC | -10 to 10 VDC | 0 to 100 mVDC |
Over/Under Range Capability | -5.25 to 11 VDC | -10.5 to 11 VDC | -.250 to 220 mVDV |
Accuracy* | ± 10 mV | ± 20 mV | ± 100 µV |
Power Requirements | 15 mA at +15 VDC | 15 mA at +15 VDC | 35 mA at +15 VDC |
*May be improved by the use of the "Set Offset" or "Set Gain" commands in the OPTOMUX command set. |
Input Response Time* | 5% of scale change in 8.5 ms 63% of scale change in 165 ms |
Resolution | 12-bits |
Isolation |
|
Temperature |
|
*AD6HS input response 100% step change in less than 3 milliseconds. |