SNAP-B3000-MODBUS SNAP Analog/Digital Brain, Modicon Modbus Protocol |
SNAP analog and digital I/O modules on a B-series rack. The brain communicates to any Modbus master device via RS-
485 using the Modbus slave protocol in both ASCII and RTU modes. Brain functions include latching, counting, on/off
status, and thermocouple linearization.
Power Requirements | 5.0–5.2 VDC at 1.0A max. |
Operating Temperature | 0 to 70 °C, 95% humidity, non-condensing |
Storage Temperature | -40 to 85 °C |
CPU | 16-bit Intel 80C196 I/O processor |
Communications Interface | RS-485/422, 2- or 4-wire, twisted pair(s), with shield |
Data Rates | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, and 115200 baud |
Range: (Multidrop Mode) | Up to 3,000 feet total length or 32 stations maximum without repeaters |
CounterFrequency Measurement | Maximum Rate: 20 kHz Minimum Pulse Width: 10 msec 16 bit |
LED Indicators | RUN (Power On), RCV (Receive), and XMT (Transmit) |
Options: Jumper Selectable | Address, Communication baud rate, RTU/ASCII |
We will inform you if the price of this product will be changed according to your wished price.