SNAP-ODC-HDB Fused breakout rack for SNAP 32-channel digital output modules |
SNAP-ODC-32-SRC. The breakout rack provides LED indicators and easily accessible fused connectors for output points.
NOTE: If you need a Factory Mutual-approved version, see the SNAP-ODC-HDB-FM.
SNAP-IDC-HDB and SNAP-IDC-HDB-FM Breakout Racks for High-Density Digital Input Modules | |
Used with | SNAP-IDC-32, SNAP-IDC-32-FM, and SNAP-IDC-32N |
Connectors | 40-pin header connects to SNAP-IDC-32 module using SNAP-HD-BF6 header cable. 32 signal input connectors; each signal connector has a corresponding common connector. For each zone of 8 signal inputs, 1 connection for either module common or field common. |
Indicators | 1 LED for each signal input (32 signal LEDs total) 1 power status LED for each zone of 8 signal inputs (4 power LEDs total) |
Fusing | 1 A fuses; 2 fuses for each zone of 8 signal inputs (8 fuses total) Replace with Pudenz 1 A automobile mini-fuse or equivalent. |
Jumpers | For each zone of 8 signal inputs, 1 jumper controls whether module common or field common is used. |
Voltage | 32 VDC maximum, 12-24 VDC nominal |
Agency Approvals | SNAP-IDC-HDB: UL, CE, RoHS, DFARS SNAP-IDC-HDB-FM: FM, CE, RoHS, DFARS |
Warranty | 30 months from date of manufacture |
SNAP-ODC-HDB and SNAP-ODC-HDB-FM Breakout Racks for High-Density Digital Output Modules | |
Used with | SNAP-ODC-32-SRC, SNAP-ODC-32-SRC-FM, SNAP-ODC-32-SNK, and SNAP-ODC-32-SNK-FM |
Connectors | 40-pin header; connects to 32-channel sourcing or sinking module using SNAP-HD-BF6 header cable. 32 signal output connectors; each signal connector has a corresponding common connector. For each zone of 8 signal outputs, 1 connection for either module common or field common. |
Indicators | 1 LED for each signal output (32 signal LEDs total) 1 power status LED for each zone of 8 signal outputs (4 power LEDs total) |
Fusing | 1 A fuses; 1 fuse for each signal output (32 signal fuses total) Replace with Pudenz 1 A automobile mini-fuse or equivalent. |
Jumpers | For each zone of 8 signal inputs, 1 jumper controls whether module common or field common is used. |
Voltage | 32 VDC maximum, 12-24 VDC nominal |
Agency Approvals | SNAP-ODC-HDB: UL, CE, RoHS, DFARS SNAP-ODC-HDB-FM: FM, CE, RoHS, DFARS |
Warranty | 30 months from date of manufacture |
We will inform you if the price of this product will be changed according to your wished price.