SNAP-ph-ORP SNAP-pH/ORP Differential Voltage Measurement Input Module |
or -0.50 to +0.50 volts. The module is ideal for differential voltage measurements and is used with pH or oxidation
reduction potential (ORP) probes for monitoring bodies of water.
The SNAP-pH/ORP module can be used with SNAP PAC brains and R-series controllers, legacy SNAP Ethernet-based
brains, and legacy serial B3000 and B3000-B brains.
Input Range | -1.00 V to +1.00 V for ORP probes -0.50 V to +0.50 V for pH probes |
Resolution | 40 µV when configured -1.00 V to +1.00 V 20 µV when configured -0.50 V to +0.50 V |
Data Freshness (Maximum) | 126 ms (63 ms per channel) when configured -1.00 V to +1.00 V 251 ms (125.5 ms per channel) when configured -0.50 V to +0.50 V |
Input Filtering | -3 dB @ 2.4 Hz |
DC Common Mode Rejection | >-120 dB |
AC Common Mode Rejection | >-120 dB at 60 Hz |
Maximum Survivable Input | ±100 VDC or peak AC |
Maximum Operating Common Mode Voltage | 250 VDC or peak AC |
Accuracy (% full scale) | 0.05% when configured -1.00 V to +1.00 V 0.05% when configured -0.50 V to +0.50 V |
Gain Temperature Coefficient | 30 PPM/°C |
Offset Temperature Coefficient | 15 PPM/°C |
Power Requirements | 5 VDC (±0.15) at 170 mA |
Input Resistance (Differential) | >10 Tera Ohms (each channel) |
Ambient Temperature: Operating Storage | 0 to 70 °C -25 to 85 °C |
Torque, hold-down screws | 4 in-lb (0.45 N-m) |
Torque, connector screws | 5.26 in-lb (0.6 N-m) |
Agency Approvals | CE, RoHS, DFARS |
Warranty | Lifetime |