120D10 120 VAC, 10 Amp, DC Control Solid State Relay (SSR) |
|
Optical Isolation Input to Output | 4,000 V |
Turn-on time | ½ cycle maximum |
Turn-off time | ½ cycle maximum |
Operating Frequency | 25 to 65 Hz (operates at 400 Hz with six times off-state leakage) |
Coupling Capacitance Input to Output | 8 pF maximum |
DV/DT Off-state | 200 volts per microsecond |
DV/DT Commutating | Snubbed for rated current at 0.5 power factor |
| 120D3 | 120D10 | 120D25 | 120D45 |
Nominal AC Line Voltage | 120 | 120 | 120 | 120 |
Nominal Current Rating (Amps) | 3 | 10 | 25 | 45 |
1 cycle Surge (Amps) Peak | 85 | 110 | 250 | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 | 1000 | 1000 | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) | 3VDC (32V allowed) | 3VDC (32V allowed) | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC | 1 VDC | 1 VDC | 1 VDC |
Peak Repetitive Voltage Maximum | 600 | 600 | 600 | 600 |
Maximum Output Voltage Drop | 1.6 volts | 1.6 volts | 1.6 volts | 1.6 volts |
Off-State Leakage (mA) Maximum | 2.5 mA | 7 mA | 7 mA | 7 mA |
Operating Voltage Range (Volts AC) | 12-140 | 12-140 | 12-140 | 12-140 |
I2t Rating t=8.3 (ms) | 30 | 50 | 250 | 1750 |
Isolation Voltage | 4,000VRMS | 4,000VRMS | 4,000VRMS | 4,000VRMS |
θjc* (°C/Watt) | 11 | 1.3 | 1.2 | 0.67 |
Dissipation (Watts/Amp) | 1.7 | 1.6 | 1.3 | 0.9 |
θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |