| DC60S5 60 VDC, 5 Amp, DC Control Solid State Relay (SSR) | 
|     | 
| DC60P or DC60MP | DC200P or DC200MP | DC60S-3 | DC60S-5 | |
| Operating Voltage Range | 5–60 VDC | 5–200 VDC | 5–60 VDC | 5–60 VDC | 
| Forward Voltage Drop | 1.5 volts at 3 amps | 1.5 volts at 1 amp | 1.5 volts at 3 amps | 1.5 volts at 5 amps | 
| Nominal Currrent Rating | 3 amps | 1 amp | 3 amps | 5 amps | 
| Off-State Blocking | 60 VDC | 250 VDC | 60 VDC | 60 VDC | 
| Signal Pick-up Voltage | 3VDC 32 Volts* allowed | 3VDC 32 Volts* allowed | 3VDC 32 Volts* allowed | 3VDC 32 Volts* allowed | 
| Signal Dropout Voltage | 1 VDC | 1 VDC | 1 VDC | 1 VDC | 
| Signal Input Impedeance | 1,000 ohms | 1,000 ohms | 1,000 ohms | 1,000 ohms | 
| 1 Second Surge | 5 amps | 2 amps | 5 amps | 10 amps | 
| Operating Temp. Range | –40 °C to 100 °C | –40 °C to 100 °C | –40 °C to 100 °C | –40 °C to 100 °C | 
| Isolation Voltage | 4,000VRMS | 4,000VRMS | 4,000VRMS | 4,000VRMS | 
| Off-State Leakage | 1 mA maximum | 1 mA maximum | 1 mA maximum | 1 mA maximum | 
| Package Type | P/MP series | P/MP series | Power series | Power series | 
| Turn-on time | 100 usec | 100 usec | 100 usec | 100 usec | 
| Turn-off time | 750 usec | 750 usec | 750 usec | 750 usec | 
| Note: *MP series maximum allowed control signal at 24 VDC. | ||||
 