G4DA10 Time Proportional AC Output |
controller. The module is optically isolated to 4,000 volts (transient) from field devices and features point-to-point
electrical isolation. The analog module mounts on any brick or modular controller and is held in place with a captive
screw. The module switches 12-280 VAC. Together with a power solid-state relay (SSR), the G4DA10 can be used to
control heater circuits.
G4DA9 | G4DA10 | |
Ambient Temperature Operating Storage | 0 °C to 70 °C - 25 °C to 85 °C | 0 °C to 70 °C - 25 °C to 85 °C |
Isolation Input-to-Output | 4,000 Vrms | 4,000 Vrms |
Turn-on Time | 50 ms | Half cycle AC waveform |
Turn-off Time | 50 ms | Half cycle AC waveform |
Output Voltage Drop Maximum Peak | 1.6 V | 1.6 V |
Operating Voltage Range | 5 - 60 VDC | 12 - 280 VAC |
Current Rating at 45 °C Ambient at 70 °C Ambient | 0.5 A 0.3 A | 0.5 A 0.3 A |
Surge Rating | 1 A for 1 second | 80 A (peak) for 1 cycle |
Off-State Leakage at Maximum Voltage | 1 mA at 60 VDC | 3 mA at 280 VAC |
Period | 2.048 seconds to 8.7 minutes 4.096 seconds default | 2.048 seconds to 8.7 minutes 4.096 seconds default |
Resolution | 12-bit Each bit = Period/4096 1 millisecond/bit default | 12-bit Each bit = Period/4096 1 millisecond/bit default |
Power Requirements | 5 V at 25 mA | 5 V at 25 mA |
We will inform you if the price of this product will be changed according to your wished price.
Review product
No review available for this product.